Maintenance Object Repair Procedures 
9-1538
STRAT-3 (Stratum 3 Clock) 
9
Stratum 3 Clock LED Strategy
NOTE:
When looking in the Stratum 3 cabinet, ‘‘A’’ card is on the left and ‘‘B’’ card 
is on the right.
NOTE:
The normal LED scheme is not followed for this device. Green LEDs do not 
indicate maintenance activity. There are no yellow LEDs, and there are 
more than three LEDs per circuit pack.
NOTE:
Removal of a card in the Stratum 3 clock may cause alarm(s) to be resolved 
and the query test to pass. However, the removed cards should still be 
replaced to restore the Stratum 3 clock to full service.
The Stratum 3 clock has the following components:
2 Clock Input cards (CI)
Provides the logic to select the better DS1 reference or Clock Input card. 
The red FAIL LED on this card indicates a failure with the card or the DS1 
reference connected to it.
2 Stratum 3 Cards (ST3)
Provides 24-hour holdover. The red FAIL LED on this card indicates a 
failure with the card. Replace the card.
2 Timing Output Cards (TOC)
Provides cable length compensation, multiple output ports, selection of 
the ST3, and CI outputs. This type of card has two red failure LEDs: one 
indicates a failure of the card; the other indicates a failure in one or more 
output ports. In either case, replace the card.
1 PBX (Private Branch Exchange) Alarm Interface (PAI)
Filters power supplied to the clock, provides fuse protection, and provides 
alarm indications based on inputs supplied by other cards. The six LEDs 
on this card provide indications for the six alarm or status conditions as 
follows:
— Loss of DS1 reference A
— Loss of DS1 reference B
— Loss of one clock unit
— Loss of both clock units
— Loss of one power supply
— Loss of both power supplies