Maintenance Architecture 
1-9
How to use the Maintenance book 
1
Screen 1-4.
Test Results screen
15. Find the Port Diagnostic Test (#35) [from the 
Test No.
 field) in the 
DID-TRK section of the Maintenance book. Note the 
Error Code
 
(61472).
16. Look in 
Table 1-3
 for Test #35 and then find “61472” in the Error Code 
column 
and “FAIL” in the Test Result column read the 
Description/Recommendation column. 
17. Perform both steps in the Description/Recommendation column.
18. Test the port (test port 01C1008 long and press 
Enter
.) again after all of 
the recommendations are exhausted.
19. If all tests pass, wait approximately 3-5 minutes for the Alarm and Error 
logs to clear.
20. Type display alarms and press 
Enter
 twice.
21. Check that the DID-TRK alarm does not appear in the log.
Field descriptions
Table 1-3. TEST #35 Port Diagnostic Test 
Error 
Code
Test 
Result
Description/Recommendation
61472
FAIL
Battery feed test failed. A problem with the incoming CO line was 
detected.
1. Check the incoming CO line for proper operation. If warranted, refer 
the problem to the CO.
2. If the CO line checks out Ok, the failure must be on the DID port. 
Replace the circuit pack.
Continued on next page
Error type
Enter error type, or blank
Error List
active-alarms, errors, or cleared-errors
Interval
h(our), d(ay), w(eek), m(onth), a(ll)
From:/To:
Specify time interval by date and time
                                  TEST RESULTS
Port      Maintenance Name  Alt. Name  Test No.  Result                Error Code
01C1008   DID-TRK                      35        FAIL                  61472