Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-227
ATM PNC-DUP (ATM PNC Duplication) 
9
PNC state of health
PNC-DUP software monitors the health of the two PNCs as determined by their 
state of health (SOH) vectors, and initiates an interchange when the health of the 
active falls below that of the standby (unless prevented from doing so by a PNC 
lock, busyout, or antithrashing mechanism). Potentially service-disrupting faults 
that occur in PNC components are reported to PNC-DUP and incorporated in the 
state of health for the affected PNC. The SOHs of both PNCs are displayed on the 
status pnc screen, as shown in 
Figure 9-11
.
Figure 9-11.
Status PNC screen with standby PNC fully In-Service
PNC state of health indexes
The Inter-PN Index form the state of health vector is used to track and compare 
the states of health of both PNCs. The fields making up the indexes are two-digit 
numbers separated by periods (.), with each field representing a different class 
of faults. The fault class fields are arranged in order of decreasing importance 
from left to right. In other words, each field in the index supersedes the following 
fields in determining which PNC is healthiest. A fault class drives an interchange 
only when all of the higher priority fault classes are equal. A zero entry indicates 
no faults present for that class. Increasing numbers indicate increasingly higher 
numbers of faults present in that class.
The Inter-PN Index contains five fields (XX.XX.XX). The Inter-PN Index reports 
faults in connectivity between port networks.
The meaning of each fault class field is given in 
status pnc                                                   page 1 of 1
                           PORT NETWORK CONNECTIVITY
                             Duplicated? yes
                        Software Locked? no
                         Standby Busied? no
                         Direct Connect? no
                      Standby Refreshed? yes
                   Interchange Disabled? no
              A-PNC                                B-PNC
           Mode: active                           Mode: standby
State of Health: functional            State of Health: functional
 Inter PN Index: 00.00.00               Inter PN Index: 00.00.00
   Major Alarms: 0                        Major Alarms: 0
   Minor Alarms: 0                        Minor Alarms: 0
 Warning Alarms: 0                      Warning Alarms: 0