Cal Flame Portable Spa User Manual

Page of 52
2009 Portable Spa
LTR20091000, Rev. A
Pr
eparing f
or 
Your Ne
w P
or
tab
le Spa
www.calspas.com
3
Always  follow  applicable  local,  state  and  federal 
codes and guidelines.
Use  only  a  dedicated  electrical  line  with  a  20  amp 
breaker.
Cord-and-plug connections may not use a cord longer 
than  15  feet  (4.6  m)  and  must  be  plugged  into  a 
dedicated 20 amp GFCI connection (NEC 680.42(A)
(2)).  Do not use extension cords!
Always use a weatherproof-covered receptacle.
Receptacle shall be located not less than 5 feet (1.5 
m) from and not exceeding 10 feet (3.0 m) from the 
inside wall of the spa.  (NEC 680.43(A))
Do not bury the power cord. If your cord becomes 
damaged, replace it before next usage.
120 Volt Electrical Installation
All 120V spas must have a GFCI. This can be either a 
20 amp GFCI receptacle or a 20 amp GFCI cord and 
plug kit as shown (CKIT110 - P/N ELE09700086).
Test the GFCI plug prior to first use and periodically 
when  the  spa  is  powered.  To  test  the  GFCI  plug 
version, follow these instructions. (Spa should already 
be plugged in and operational.)
Press the TEST button on the GFCI. The GFCI will 
1. 
trip and the spa will stop operating.
Press the RESET button on the GFCI. The GFCI 
2. 
will reset and the spa will turn back on.
The spa is now safe to use.
If the GFCI trips while the spa is in use, press the 
RESET button. If the GFCI does not reset, unplug the 
spa and call your local Cal Spas dealer for service. DO 
NOT USE THE SPA!
All  240V  spas  must  be  permanently  connected 
(hardwired) to the power supply. These instructions 
describe  the  only  acceptable  electrical  wiring 
procedure. Spas wired in any other way will void your 
warranty and may result in serious injury.
This is the only acceptable electrical wiring procedure. 
Spas wired in any other way will void your warranty. 
See the wiring diagram on page 6.
When  installed  in  the  United  States,  the  electrical 
wiring  of  this  spa  must  meet  the  requirements  of 
National  Electric  Code,  ANSI/NFPA  70-2008  and 
any  applicable  local,  state,  and  federal  codes.  The 
electrical  circuit  must  be  installed  by  an  electrical 
contractor and approved by a local building / electrical 
inspector.
GFCI and Wiring Requirements
The power supplied to the spa must be on a dedicated 
GFCI protected circuit as required by ANSI/NFPA 70 
with no other appliances or lights sharing the power.
Use  copper  wire  with  THHN  insulation.  Do  not  use 
aluminum wire.
Use  the  table  on  the  next  page  to  determine  your 
GFCI and wiring requirements.
240 Volt Electrical Installation
When NEC requires the use of wires larger than #6 
AWG, install a junction box near the spa and use #6 
AWG wire between the junction box and the spa.
Wire  runs  over  85  feet  must  increase  wire  gauge 
to  the  next  lower  number.  For  example:  A  normal 
50  amp  GFCI  with  four  #8  AWG  Copper  wires  run 
over 85 feet would require you to go to four #6 AWG 
copper wires.
Read  and  follow  the  heater  manufacturer’s  safety 
and installation instructions prior to installation and 
operation.  Incorrect  installation  may  damage  the 
heater and void its warranty.
Testing the GFCI Breaker
Test the GFCI breaker prior to first use and periodically 
when the spa is powered. To test the GFCI breaker 
follow these instructions (spa should be operating):
Press the TEST button on the GFCI. The GFCI will 
1. 
trip and the spa will shut off.
Reset the GFCI breaker by switching the breaker 
2. 
to  the  full  OFF  position,  wait  a  moment,  then 
turn the breaker back on. The spa should have 
power again.