GE GFK-1918D User Manual

Page of 114
G E   F a n u c   P L C   Ta r g e t s
Configuring Communication
28
CIMPLICITY Logic Developer - PLC Version 4.00
GFK-1918D
3
C O N F I G U R I N G   C O M M U N I C A T I O N
In order for Logic Developer - PLC to communicate with a target PLC, a 
connection must be properly configured. The properties of a target are adjustable 
to accommodate your connection(s).
To  co nfig ur e a n E ther net  or  s er ial  co nn ec t ion
1.
In the 
 Project tab of the 
 Navigator, right-click a  
target and choose Properties.
The Inspector opens showing the target’s properties. 
2.
In the 
Inspector, set the Physical Port property to Ethernet or a COM port (or a modem if one is installed). 
3.
If the Physical Port is Ethernet, enter the IP Address of the target PLC. 
Note: You can connect to a GE Fanuc PACSystems™ RX7i by means of Ethernet 
only.
4.
Double-click Additional Configuration to access the detailed settings for your connection. 
Note: Serial communication with a non-PACSystems™ PLC is always available if it 
is the only device connected and an SNP_ID is not specified. An IP address must 
be set in the PLC before an Ethernet link can be established. 
C o n f i g u r i n g   C o m m u n i c a t i o n   f o r   P A C S y s t e m s ™
The only communication method supported by a PACSystems™ is Ethernet. This 
ensures fast communication, because every PACSystems™ has an embedded 
Ethernet adapter.
To  co nfig ur e  c o mmu nic at ion   wit h  a   P ACS ys t em s ™  RX 7i
1.
Physically connect the PACSystems™ RX7i to the Ethernet network.
2.
Set up a temporary IP address. For more information, see “To set a temporary IP address for a PACSystems™ RX7i”.
The temporary IP address enables you to communicate with the PACSystems™ 
RX7i the first time. 
3.
Do one of the following:
If there is already a hardware configuration stored on the PACSystems™ RX7i 
target, it contains a permanent IP address. To obtain this permanent IP address 
from the PACSystems™, upload the hardware configuration from the 
PACSystems™ RX7i.
- OR -
Want to know more? In the Help Index, look up “Configuring a direct connection”.