Siemens C79000-G8976-C156-07 User Manual

Page of 300
18
DCOM Settings with the dcomcnfg System Program
273
Commissioning PC Stations - Manual and Quick Start
Release 5/2005
C79000-G8976-C156-07
18.7
Configuration of the Client Computer
Overview
When operating with DCOM, this situation is that the OPC server runs on a
different computer from the OPC clients (applications). This is why no process for
the OPC server is visible in the Windows Task Manager of the client computer.
To allow the OPC clients to access the OPC server, the following requirements
must be met for this mode:
S
Registering the OPC server
The OPC server and its location must be registered on the client computer. This
registration is necessary so that the COM library knows the required object
making configuration possible.
You must specify the user account will be used to access the OPC server.
The procedure is described below.
S
Providing “OPC proxy” libraries
The OPC Proxy libraries provided by the OPC Foundation are also required on
the client computer. This library converts the COM calls into a data stream for
transmission over the network.
You should also read the notes on how to install a client in the Installation
Instructions.
S
Registering the OPC client
When necessary access rights and security settings must be made for the OPC
clients. As shown below in the example of the OPC Scout, the default setting
assumes an open system and assumes that the user will adapt the settings
when higher security is required.
Make the required settings analogous to the description of configuring the
server computer in Section 18.6. Below, you will find instructions on registering,
for example the OPC Scout as a client .