SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the 
temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.
Rate (P700 to P707) 
These parameters determine how material level changes are reported.
P700 Max Fill Rate
Adjusts the SITRANS LU01 response to increases in the actual material level (or advance 
to a higher Failsafe Material Level, P071). 
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units 
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process 
Speed (P003) is altered. 
P701 Max Empty Rate
Adjusts the SITRANS LU01 response to decreases in the actual material level (or advance 
to a lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units 
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process 
Speed (P003) is altered. 
Values
Range: 0.000 to 9999
Altered by
 P003 Maximum Process Speed
Related
P005  Units
P007  Span
P071 Failsafe Material Level
P003 Value
Meters/Minute
1
0.1
2
1
3
10
Values
Range: 0.000 to 9999
Altered by
P003 Maximum Process Speed
Related
P005 Units
P007 Span
P071 Failsafe Material Level
P003 Value
Meters / Minute
1
0.1
2
1
3
10