This feature may only be used to adjust the delay before the next point is scanned. Enter 
the amount of delay in seconds. This value is automatically altered when Maximum 
Process Speed (P003) is altered. 
P728 Shot Delay
The delay, in seconds, between transducer shots.
Use this if transient acoustic noise within the vessel is causing measurement difficulties 
due to echoes from one shot being received on the next. If more than one ultrasonic unit 
is installed for redundancy, this value should be 0.
P729 Scan Time
View the elapsed time (in seconds) since the point displayed was last scanned. 
This may be viewed as an Auxiliary Reading in the RUN mode.
Display (P730 to P733) 
P730 Auxiliary Reading
Use this feature to display operator selected Auxiliary Readings temporarily or 
indefinitely (as desired).
Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary 
Readings until another Auxiliary Reading is selected or programming mode is entered. 
See the 
Keypad 
section on page 24 for RUN mode auxiliary readings.
Selecting the Auxiliary Reading operation
1.
Press READING 
 to display the Auxiliary Function symbol.
2.
Press ARROWS 
 
 to access the OFF or HOLd option desired. 
3.
Press ENTER 
.
If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That 
value will show in the auxiliary reading area by default. Other values are available but will 
reset to the parameter defined here.
Values
Range: 0.1 to 4.0
Preset: 0.5
Values
Range: 0.000 to 9999 (view only)
Related
 
P001  Operation
Values
Range: 000 to 999
Display: OFF, HOLd