Parameter Settings for Point # 1 
Parameter Settings for Ma Output #1 
Parameter Setting for Temperature Averaging 
With process control equipment disabled, enter the RUN mode to monitor system 
performance and alarm programming. (A Reading Measurement simulation (P920) may 
be performed to verify mA output programming). 
When satisfied with system performance and programming, connect mA output 1 to the 
Programmable Logic Controller (PLC). 
Note that on power off the mA output drops to 0.00 mA. During a power interruption, the 
last known mA output value is maintained in memory for 1 hour minimum. If power is 
interrupted beyond 1 hour, on power resumption, the mA output immediately assumes the 
new value. 
Number
Description
Instructions
P001
Operation
Enter "2" for 
space
P002
Material
No entry required (preset for 
liquid)
P003
Measurement Response
Enter "4" for 
surge
 (100 m/min, Failsafe Timer = 0.1 
minutes). 
P004
Transducer
Enter "101" for 
XCT-8
P005
Units
Enter "4" for 
feet
P006
Empty
Enter "4.5" for 
4.50 ft
 (3 feet diameter plus 1.5 ft in 
standpipe). 
P007
Span
Enter "3" for 
3 ft
 (vessel diameter). 
P070
Failsafe Timer
No entry required, (preset by P003). 
Number
Description
Instructions
P200
mA Range
No entry required. (preset for 
20 mA = low level
P001 = 2.) 
P213
mA Max Limit
Enter "22" for 
22.00 mA
P219
mA Failsafe
Enter "20.2" for 
20.20 mA
Number
Description
Instructions
P660 
Temp Source
Enter "5" for average XCT-8 and TS-3 temperatures.