APC Command Line Interface User Manual

Page of 39
Command Reference: Switched Rack PDU Commands
28
Command Line Interface (CLI) User’s Guide
overloadrestriction
Syntax to read the overload restriction: 
overloadrestriction [phase_number]
Syntax to set the overload restriction: 
overloadrestriction phase_number setting
Description: 
When the overload restriction is set 
to on, the command prevents outlets from turning 
on while the overload alarm threshold is violated. 
• To read the current setting, omit setting in the 
command line.
• To change the current setting, include the 
phase number and the new value for setting 
(on or off) in the command line.
Access: 
Administrator and device manager 
(device-only user).
Parameters: 
Output Format when reading the setting: 
OK
Overload restriction is setting for phase_number.
Output Format when changing the setting: 
OK
Setting overload for phase_number to setting.
Error Messages: 
E101, E104
phase_number  The number (1, 2, or 3) of the phase 
whose overload restriction setting you 
want to read or set. If you omit the 
phase number when reading the 
setting, the command by default reads 
the setting for phase 1.
setting 
The available settings, on and off, are 
not case-sensitive.