Command Reference: Switched Rack PDU Commands
26
Command Line Interface (CLI) User’s Guide
nearoverloadwarning
Syntax (to read the nearoverload alarm 
threshold):  
nearoverloadwarning [phase_number]
Syntax (to set the nearoverload warning 
threshold): 
nearoverloadwarning phase_number current
Description: 
Set or read the near-overload 
warning threshold.
Parameters: 
Access: 
Administrator or device manager 
(device-only user).
Output format, reading the near-overload 
alarm threshold: 
OK
Near overload warning threshold is currentA.
Output format, setting the near-overload alarm 
threshold: 
OK
Setting near overload warning threshold for 
phase_number to currentA.
Error Messages: 
E101, E104
phase_number  The number (1, 2, or 3) of the phase 
whose near-overload warning 
threshold you want to read or set. The 
default is phase 1. 
current 
The threshold, in amps, to set for the 
phase specified as phase_number.