Using the LED Indicators and Display for Troubleshooting
Section 14-2
---
---
E3
Server Con-
nection Error
An error 
occurred in 
communica-
tions with the 
DNS server.
The DNS Server 
Error Flag (n+14, bit 
05) will turn ON.
03C4
De-
tails: 
00xx
Perform one of the 
following:
• Correct the DNS 
server settings.
• Check the com-
munications path 
(EtherNet/IP Unit 
or built-in 
EtherNet/IP port, 
cable connec-
tions, hubs, rout-
ers, and servers) 
and correct any 
problems.
An error 
occurred with 
the BOOTP 
server.
1. There was no 
response 
from the 
BOOTP serv-
er.
2. The BOOTP 
server at-
tempted to 
set an invalid 
IP address in 
the EtherNet/
IP Unit or 
built-in Ether-
Net/IP port.
Case 1:
The Unit will continue 
sending requests to 
the BOOTP server 
until there is a 
response. In the 
meantime, the Unit 
will be offline and 
unable to communi-
cate. Errors will be 
returned to all com-
munications requests. 
Data exchanges 
(refreshing) will con-
tinue with the CPU 
Unit.
Case 2:
The Unit will operate 
with the default IP 
address 
(192.168.250.node_
address).
The Unit Error 
Occurred Flag (n+10, 
bit 00), Network Error 
Occurred Flag (n+10, 
bit 01), and BOOTP 
Server Error Flag 
(n+14, bit 10) will go 
ON.
03C4
De-
tails: 
06xx
Perform one of the 
following:
• Correct  the 
BOOTP server 
settings.
• Check the com-
munications path 
(EtherNet/IP Unit 
or built-in 
EtherNet/IP port, 
cable connec-
tions, hubs, rout-
ers, and servers) 
and correct any 
problems.
An error 
occurred in 
communica-
tions with the 
STNP server.
The SNTP Server 
Error Flag (n+14, bit 
11) will turn ON.
03C4
De-
tails: 
03xx
Perform one of the 
following:
• Correct the SNTP 
server settings.
• Check the com-
munications path 
(EtherNet/IP Unit 
or built-in 
EtherNet/IP port, 
cable connec-
tions, hubs, rout-
ers, and servers) 
and correct any 
problems.
Indicator
Error
Cause
Unit operation (Flag 
status)
Error 
log
(hex)
Countermeasure
MS
NS
7-segment