Connection Status Codes and Error Processing
Section 14-3
Errors Related to the Unit
The 7-segment display alternates between the node address and error code.
14-3 Connection Status Codes and Error Processing
This section explains how to identify and correct errors based on the tag data
link’s connection status. The connection status can be read using the Connec-
tion
 Tab Page of the Network Configurator’s Monitor Device Window. For
details, refer to 14-1-1 The Network Configurator’s Device Monitor Function.
Note
1.
The connection status has the same meaning as the Connection Manag-
er’s General and Additional error response codes, as defined in the CIP
specifications.
2.
The Open DeviceNet Vendor Association, Inc. (ODVA) can be contacted at
the following address to obtain a copy of the CIP specifications.
ODVA Headquarters
4220 Varsity Drive, Suite A
Ann Arbor, Michigan 48108-5006
USA
TEL: 1 734-975-8840
FAX: 1 734-922-0027
Flashing 
red
Not lit
F4
Communica-
tions Control-
ler Error
An error 
occurred in the 
Communica-
tions Controller 
in the EtherNet/
IP Unit or built-in 
EtherNet/IP 
port. 
• The Unit will be 
offline and unable to 
communicate. Errors 
will be returned to all 
communications 
requests.
• Data exchanges 
(refreshing) will con-
tinue with the CPU 
Unit.
The Unit Error 
Occurred Flag (n+10, 
bit 00), Network Error 
Occurred Flag (n+10, 
bit 01), and Commu-
nications Controller 
Error Flag (n+10, bit 
05) will go ON.
020F
Replace the Ether-
Net/IP Unit or (for 
the built-in Ether-
Net/IP port) the 
CPU Unit if the 
error recurs when 
the Unit is 
restarted.
Flashing 
red
---
C8
Node Address 
Setting 
Changed Dur-
ing Operation
The Node 
Address Setting 
Switch was 
changed during 
operation.
Operation will con-
tinue.
The IP Address 
Changed During 
Operation Flag (n+11, 
bit 02) will turn ON.
---
Restart the Ether-
Net/IP Unit or built-
in EtherNet/IP port 
after setting the 
correct node 
address.
Indicator
Error
Cause
Unit operation (Flag 
status)
Error 
log
(hex)
Countermeasure
MS
NS
7-segment
Indicator
Error
Cause
Unit operation (Flag 
status)
Error 
log
(hex)
Countermeasure
MS
NS
7-segment
Lit red
Not lit
---
Special Unit 
Error
An error 
occurred in a 
Special I/O Unit 
or CPU Bus 
Unit.
Records the error in 
the error log.
Operation stops.
0601
Restart the CPU 
Unit. 
Replace the Ether-
Net/IP Unit or (for 
the built-in Ether-
Net/IP port) the 
CPU Unit if the 
error recurs.