MX28B-1200   PRODUCT MANUAL 
MX28B-1200/2400 
17 
5.3  Battery Connections  
5.3.1 Battery Disconnect 
An external circuit breaker (not supplied) is required in the negative line (located at the battery 
end) to protect the cables from the battery to the MX28B dc power plant.  The power plant can 
monitor auxiliary contacts from this breaker.  Selection of a circuit breaker for a battery string 
should take into account maximum battery short circuit current and cable sizing. 
5.3.2  Cable Sizing Considerations 
The battery cable(s) should be sized 
sufficiently large to limit the voltage drop from 
the MX28B dc power plant to the battery 
during charging per system design 
requirements.  The cable(s) must also carry the 
full load current during battery operation.  If 
assistance is required to determine the 
necessary cables for the application, contact 
your sales representative or APC. 
5.3.3  Connecting the Cables 
The battery cable connections are located at the 
top rear of the unit as shown in Figure 5-4.  
The battery positive (return bus) and battery 
negative (-48V bus) buses each provide four 
sets of 3/8”-16 holes on a double pattern one-
inch and 1 ¾-inch centers for connecting two-
hole battery cable lugs.  Connect the battery 
cables as applicable using 3/8”-16 bolts (not 
provided) and tighten them with a torque 
wrench to 200 in-lbs. 
*****
   CAUTION   
*****
 
Make certain that the battery polarity is correct when making connections to the Model 
MX28B dc power plant.  Incorrect connection could cause severe equipment damage. 
5.4  DC SYSTEM GROUNDING 
THE POSITIVE LOAD CONNECTION (RETURN BUS) FOR THE POWER PLANT 
MUST BE CONNECTED TO THE FACILITY MASTER STATION GROUND.   THE 
CONNECTION SHOULD BE MADE ON THE RETURN BUS IN THE BASE UNIT 
DISTRIBUTION AREA.  DETAILS FOR THIS CONNECTION SHOULD BE 
PROVIDED IN THE SITE ELECTRICAL GROUNDING PLANS. 
 
 
 
+
-
Battery Positive (+)  
Battery Negative (-) 
Figure 5-4  Battery Connections