MX28B-1200   PRODUCT MANUAL 
MX28B-1200/2400 
19 
  
5.6.2 Control Wiring 
Cables for controlling and monitoring the rectifiers and circuit breakers/fuses must be run from 
expansion frames to the control unit in the base frame.  There are three basic cables used for 
these functions: 
•= The AWA-0970 ten-pin ribbon cable connector handles serial communications for rectifier 
reporting and control.  This cable connects to the J1 connector of the DC/DC converter 
PCB’s (EAA-0111) in each power box frame. 
•= Circuit breaker reporting in extension power and distribution bays is communicated back to 
the control unit through the AWA-0972 cable.  This cable is connected to J15 on the control 
unit interface PCB in the base unit and runs to connector J2 on the Alarm Extension PCB 
(EAA-0072) in the remote bay.  Additional bays are connected via the same cable, which 
connects up to four Alarm Extension PCB’s. 
•= Fuse reporting is routed from the Fuse Sense PCB (ADV-1204) to the control unit via cable 
AWA-0967. 
Refer to Figure 5-6 for a pictorial representation of multi-bay cable connection.  Figure 5-7 
shows the information as a wiring diagram.