Siemens PANEL PC 877 User Manual

Page of 288
 
SIMATIC Panel PC 877 
Operating instructions, Release 07/2006, A5E00877780-01 
15-1
 
Technical data 
15
15.1 
15.1 
General technical data 
 
 
General technical data 
AC device: Supply voltage 
100 to 240 V AC (85 to 265 V AC) 
DC device: Supply voltage 
24 V DC (20.4 to 28.8 V DC) SELV 
AC device: Frequency  
50 - 60 Hz (47 to 63 Hz) 
Transient voltage interruption  
according to Namur 
AC device: At least 20 ms for 93 to 264 V  
at most 10 events per hour; recovery time of at least 1 s  
DC device: no buffering 
AC device: Max. power consumption of complete unit 
at 240 W secondary 
360 W primary with approx. 65% efficiency 
DC device: Max. power consumption of complete unit 
at 180 W secondary 
265 W primary with approx. 70% efficiency 
AC device: max. current output 
+5 V/25 A *
)
 
+3.3 V/10 A *
)
 
*) 155 W total allowed 
+12 V/12.2 A peak 14.0A 
–12 V/0.8 A  
–5 V/0.5 A limited to >0.8 A 
+5 Vaux/2 A peak 2.5 A 
The total voltage amounts to max. 230 W. 
DC device: max. current output 
+5 V/22 A *
)
 
+3.3 V/16 A *
)
 
*) 140 W total allowed 
+12 V/4.4 A peak 8.0 A 
–12 V/0.5 A  
–5 V/0.5 A  
+5 Vaux/1 A 
The total voltage amounts to 180 W. 
Noise emission 
< 55 dB(A) according to DIN 45635-1 
Degree of protection for complete unit on rear 
IP 20 
Degree of protection on front with tension jack 
mouniting 
IP 65 
Degree of protection on front with screw mouniting 
IP 54