Intelligence Panel PCs are designed for installation in switchboard panels and cabinet 
doors. To facilitate installation and access to connectors, switchboard panels and 
consoles must be accessible from the rear. The unit can be installed in switchgear 
cubicles or cabinets with wall thicknesses of 2mm to 13mm (0.079 – 0.5 inches). For 
optimum sealing with the cabinet face, the recommended wall thickness is 
3mm (0.118 inches). 
Air Inlets and outlets must have at least 25mm (approx. 1.0 inch) of space around them 
and not be obstructed. Adequate airflow around the exterior of the unit is important to the 
interior temperature of the unit. Two fans are used to create air flow through the industrial 
computer to maintain a correct working temperature.  
 
Caution 
Only correct mounting ensures front-side NEMA and IP65 protection 
Caution 
The IC5005/BC5005 and IC5008/BC5008 units must be installed and 
operated in a vertical position to ensure the correct operating 
position of the CD-ROM drive. 
Caution 
Viewed from the front, there must be sufficient space (132 mm or 
5.20 in. minimum) to the left of the units to allow the CD-ROM drive 
drawer to open. 