Installation Procedures 
1.  Make a cut-out (corresponding to size of the particular unit) in the switchgear panels 
or cabinet doors (see Figures 3-1 through 3-3). 
2.  Insert the unit into this cut-out from the front. 
3.  Insert the mounting screws together with mounting blocks in the slots provided in the 
metal cover and tighten all screws evenly until the surround panel covers the cut-out 
securely. Maximum torque is 0.25 N-m (2.2 lb
f
-in). 
Caution 
Over tightening the screws will cause irreparable damage to the 
front panel and break the touch screen itself. 
Connect the provided power cord to the AC power supply. If additional grounding to a 
grounding screw is desired, use 14 AWG gauge wire minimum. 
Table 3-1. Critical Dimensions for Installation 
Dimension IC5002 
BC5002 
IC5005 
BC5005 
IC5008 
BC5008 
Cover (W x H) 
313 x 252mm 
23.3 x 9.9 in. 
373.6 x 295.6 mm 
14.7 x 11.6 in. 
426 x 355mm 
16.8 x 14.0 in. 
Cutout (recess) (W x 
H) 
318 x 256mm +1.0mm
12.5 x 10.1 in. + 0.04 
in. 
376 x 299mm +1.0mm 
14.8 x 11.8 in. + 0.04 
in. 
428 x 358mm +1.0mm
16.9 x 14.0 in. + 0.04 
in. 
Space required for 
ventilation 
Minimum 50mm (2 in) clearance at top and bottom of the unit. Minimum 
30mm (1.2 in.) at sides. 
Note additional side space consideration is required for models with CD-
ROM, depending on cabinet design. Viewed from the front, there must be 
sufficient space (132 mm or 5.20 in. minimum) to the left of the units to 
allow the CD-ROM drive drawer to open. 
Mounting depth 
177mm 
6.97 in. 
150mm 
5.9 in. 
154mm 
6.1 in.