GFK-2023C 
Chapter 3  Installation 
3-7 
3
 
  
 
Nonincendive Field Wiring Control Drawing CD-E219479  
for USB Port Connections 
Hazardous (Classified) Location 
Class I, Division 2 Groups A, B, C, and D 
Front USB Port on Computer No._________________ 
Nonincendive Field
Wiring Apparatus
Associated Nonincendive
Field Wiring Apparatus
(Computer)
Vmax
Imax
Ci
Li
Voc
Isc
Ca
La
 
Notes: 
1. Nonincendive 
Circuit 
Parameters: 
Voc = 4.969 VDC 
Isc = 2.06 A 
Ca = 75 µF 
La = 40 µH 
2.  Selected Nonincendive Field Wiring Apparatus shall satisfy the following: 
Voc 
≤ 
Vmax 
Isc 
≤ 
Imax 
Ca 
≥ 
Ci + C cable 
La 
≥ 
Li + L cable  
 
3.  If the electrical parameters of the cable are unknown, the following values may be 
used: 
Capacitance – 60 pF/ft 
Inductive – 0.20 µH/ft 
4.  Nonincendive Field Wiring must be installed in accordance with Article 501.4(B)(3) of 
the National Electrical Code ANSI/NFPA 70. 
5.  Selected Nonincendive Field Wiring Apparatus must not be connected to external 
power source.