Emerson GXT 10KVA User Manual

Page of 32
Cable Installation
20
Figure 13 Connecting Maintenance Bypass to GXT10000T-208X
!
CAUTION
It is mandatory to connect exactly as shown.
NOTE
1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a single 
source, the input connection may be made to either TB1 or TB2.
2. DUAL-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a dual source, 
the UPS input supply connection must be made to TB1 and the bypass input supply 
connection must be made to TB2. The jumpers between TB1 and TB2 must be removed.
3. If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel 
board connected to the output terminal TB5.
TB4
TB2
TB1
TB3
TB5
G
G
G
G
G
G
1
1
2
3
4
2
3
4
L1
L2
L1
L2
N
N
Input
Output
External Battery
GXT10000T-208X
N
FINITY
 M
AINTENANCE
 B
YPASS
 C
ABINET
 W
ITHOUT
 
T
RANSFORMER
L1 L2
L1
L2
L1
L2
L2A
N
208V
120V
120V
GEC
Remove these three wires 
for dual source
(see NOTE 
below)
Flexible 
conduit
Flexible 
conduit
Input 2
Input 1