Cable Installation
21
Figure 14 Connecting Maintenance Bypass to GXT10000T-240X
NOTE
1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a single 
source, the input connection may be made to either TB1 or TB2.
2. DUAL-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a dual source, 
the UPS input supply connection must be made to TB1 and the bypass input supply 
connection must be made to TB2. The jumpers between TB1 and TB2 must be removed.
TB4
TB2
TB1
TB3
TB5
G
G
G
G
G
G
1
1
2
3
4
4
L1
L2
L1
L2
N
N
Input
Output
External Battery
GXT10000T-240X
L1 L2
L1
L2
L1
L2
N
FINITY
 M
AINTENANCE
 B
YPASS
 C
ABINET
 W
ITHOUT
 
T
RANSFORMER
N
240V
120V
120V
3
2
GEC
Remove these three wires 
for dual source
(see NOTE 
below)
Flexible 
conduit
Flexible 
conduit
Input 2
Input 1