38      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
2. Actual battery capacity   
The monitoring module can approximately calculate the remaining battery capacity 
in real time. Through configuration at the host, the remaining battery capacity can 
be displayed in the mode of percentage, remaining Ah or remaining time, etc. The 
default is the percentage.   
During the normal BC/FC management, the monitoring module regards the rated 
capacity as the capacity that each battery group can reach. When the battery 
discharges, the monitoring module will calculate the battery remaining capacity 
according to the discharge current, discharge time and the preset “battery 
discharge curve”. When the battery is being charged, the monitoring module will 
calculate the real-time battery capacity according to the detected charge current, 
charge time and preset “battery charge efficiency”. If the calculated battery 
remaining capacity is higher than the rated capacity, the monitoring module will 
automatically change the calculated battery remaining capacity to the rated 
capacity. 
AC information page   
There is no AC data acquisition board in ACTURA Flex 48330
 
Power System,so 
the configuration of “AC Input” can only be set to “None”. 
BC prompt and temperature information page 
System Power: 
  23%  
Cyc BC After: 
  55h  
 
 
 
Bat. Temp: 
      25°C   
Amb. Temp: 
                      5°C   
 
 
 
If the monitoring module bans BC and no temperature sensor is configured, this 
page will not be displayed.   
The first line of the information page displays the BC prompts, which will be 
different with different systems, including:   
1. Prompt the time of next Cyclic Boost according to the battery state   
2. If BC is going on, the “Charging” will be prompted 
3. If BC is disabled, this row will be empty