Chapter 5  Operating SCU      39 
ACTURA Flex 48330
 
Power System  User Manual 
The 2
nd
 and 3
rd
 rows of the page are the temperature information detected by the 
temperature sensor. The display will vary with different parameter settings (see 4.7 
for parameter setting). If the temperature sensor is not connected or is faulty, 
system will prompt invalid. Meanwhile, the 4
th
 row will display “Check Temp 
Sensor”. 
5.4  Querying Rectifier Status 
The rectifier information includes the rectifier serial No., voltage, current, current 
limit, mains situation, rectifier power limit and temperature power limit.   
1. At any page of the system information, press “ENT” to enter the main menu.   
2. Use “
” or “
” keys to select the “Status” sub-menu in the main menu, and 
press “ENT” to confirm. 
Status               
Rectifiers    
Active Alarm 
Alarm History 
       
 
3. Use “
” or “
” to select the “Rect Info” submenu, as shown in the above figure. 
Press “ENT” to confirm. 
  Rect 1: 01234567   
      54.1V    30.2A     
      AC On    DC on   
AC Volt:  220V 
             
 
Rect 1: 01234567   
CurrLimit:    34%  
AC Derated:          Y   
Temp Derated:  N  
       
 
The information of every rectifier is displayed in two pages. The information in the 
first page includes: rectifier serial No., output voltage and current, AC/DC on/off 
state and AC input voltage. The information in the second page includes: rectifier 
serial No., current limit, the states of “AC Derated” and “Temp Derated”. Press “
” 
to scroll to the next page, or “
” to return to the last.   
4. Press “
” or “
” to query other rectifier’s information.   
At most 48 pieces of rectifier’s information can be displayed. If the rectifier does not 
exist, there will be no information. If the rectifier communication is interrupted, the 
information will be displayed in high light.