Chapter 5  Operating SCU      49 
ACTURA Flex 48330
 
Power System  User Manual 
Table 5-6    Logic matrix used for configuring 8 dry contacts 
Setting 
0,1 Alarm SN Logic Alarm SN  Logic  Alarm SN
 
Column(B)
Row(A) 
Dry Contact 0 
 
 
 
 
 
 
Dry Contact 1 
 
 
 
 
 
 
Dry Contact 2 
 
 
 
 
 
 
Dry Contact 3 
 
 
 
 
 
 
Dry Contact 4 
 
 
 
 
 
 
Dry Contact 5 
 
 
 
 
 
 
Dry Contact 6 
 
 
 
 
 
 
Dry Contact 7 
 
 
 
 
 
 
 
The format of PLC setting is AlarmPLC[A][B]=C. 
Where, “A” is the row No., and “B” is the column No., and “C” is the value of the 
matrix element. An example is shown in the following table: 
Table 5-7    Example of PLC setting 
PLC byte 
Byte description 
Function 
AlarmPLC[3][0]=1 
Elemant value of Row 3 and Column 0 is 1. 
Use Dry Contact 3 
AlarmPLC[3][1]=1 
Elemant value of Row 3 and Column 1 is 1. 
Alarm SN of Fuse 1 Blow up
AlarmPLC[3][2]=3 
Elemant value of Row 3 and Column 2 is 3. 
AND Logic 
AlarmPLC[3][3]=2 
Elemant value of Row 3 and Column 3 is 2. 
Alarm SN of Fuse 2 Blow up
AlarmPLC[3][4]=3 
Elemant value of Row 3 and Column 4 is 3. 
OR Logic 
AlarmPLC[3][5]=43  Elemant value of Row 3 and Column 5 is 43.  Alarm SN of LLVD 
 
For the above PLC setting: When alarms of “Fuse 1 Blow up” and “Fuse 2 Blow up” 
occur at the same time, or LLVD occurs, dry contact 3 will output the alarm signal. 
Relationship between PLC SN and Alarm: 
Table 5-8    PLC SN and Alarm 
PLC 
SN 
Alarm 
description 
Remark 
Alarm Block 
Disabled for China Market, Enabled for rest of world 
Load 1 Failure 
 
Load 2 Failure 
 
Load 3 Failure 
 
Load 4 Failure 
 
Load 5 Failure