Chapter 5  Operating SCU      51 
ACTURA Flex 48330
 
Power System  User Manual 
PLC 
SN 
Alarm 
description 
Remark 
41 
Short Test Error 
 
42 BattTest 
Error 
 
43 LLVD 
 
44 BLVD 
 
45 Outvolt 
Error 
 
 
46 Power 
Failure 
 
47 
Multi-Rect Fails 
Disabled for China Market, Enabled for rest of world 
48 
Rect Fan Fails 
 
49 
Rect Com Failure 
 
50 
Rect Vac Err 
 
51 Rect 
Over 
Temp   
52 Rect 
Failure 
 
53 Rect 
Protect 
 
54 
Rect Fan Fails 
 
55 Rect 
PowerLimit   
56 Derateby 
Temp   
 
5.6  Maintenance 
 Note 
1. This operation can be conducted only when the battery management is set to “Manual”.   
2. Be careful! BLVD operations may result in power interruption. 
 
Operation Procedures: 
1. At any information page, press “ENT” to enter the main menu.   
2. Press “
” to select the “Maintenance” menu.   
You cannot enter the system Maintenance menu if the “Battery Management” is set 
to “Auto”.   
3. Press “ENT” and input the correct operation password. Press “ENT” again to 
enter the “Maintenance” menu. 
 
Enter Password: 
123456