Emerson 1000 User Manual

Page of 32
Specifications
24
Table 8
Liebert PSI XR battery run times
Number of Batteries
Load %
1000
1500
2200
3000
Internal Battery
10
83
82
76
75
20
52
48
48
47
30
31
28
28
28
40
18
17
17
17
50
15
13
14
13
60
12
11
11
11
70
11
9
9
9
80
9
7
8
7
90
7
6
7
6
100
6
5
5
5
Internal battery
+ 1 External
Battery Cabinets
10
263
222
161
143
20
165
131
101
83
30
120
93
69
60
40
95
68
55
47
50
73
56
45
32
60
62
47
31
27
70
54
33
27
18
80
48
29
18
16
90
43
26
17
14
100
32
18
15
12
Internal battery
+ 2 External
Battery Cabinets
10
439
357
242
205
20
275
212
152
127
30
200
150
111
92
40
157
116
82
68
50
129
95
68
56
60
110
76
57
47
70
96
65
50
33
80
80
58
44
30
90
71
52
32
26
100
65
47
29
18
Internal battery
+ 3 External
Battery Cabinets
10
614
492
322
267
20
385
291
202
166
30
280
207
147
120
40
220
160
116
94
50
181
131
96
73
60
154
111
77
62
70
134
95
67
54
80
119
79
59
47
90
106
71
53
43
100
96
64
48
31
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.