Emerson 1000 User Manual

Page of 32
Specifications
25
Internal battery
+ 4 External
Battery Cabinets
10
790
627
483
330
20
494
371
303
204
30
360
264
221
148
40
283
204
174
116
50
233
167
143
95
60
198
141
122
76
70
172
122
106
66
80
152
108
94
59
90
137
96
79
52
100
124
82
72
48
Internal battery
+ 5 External
Battery Cabinets
10
965
762
564
392
20
605
452
354
243
30
440
320
258
176
40
346
248
203
138
50
265
203
167
113
60
242
171
142
96
70
211
148
124
79
80
186
131
110
70
90
167
117
98
62
100
151
106
84
56
Internal battery
+ 6 External
Battery Cabinets
10
1140
897
644
454
20
714
531
405
281
30
520
377
295
204
40
408
292
232
160
50
337
239
191
131
60
286
202
163
112
70
249
175
142
97
80
220
154
125
81
90
197
138
112
72
100
179
124
102
65
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
Table 8
Liebert PSI XR battery run times (continued)
Number of Batteries
Load %
1000
1500
2200
3000