6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
34 
Operating Instructions (Compact) 
6.4 
Commissioning the application 
An application is commissioned to adapt/optimize the frequency inverter - motor 
combination to the particular application. The frequency inverter offers numerous 
functions - but not all of these are required for the particular application. These 
functions can be skipped when commissioning the application. A large proportion 
of the possible functions are described here; refer to the parameter list for 
additional functions. 
Parameters, designated with a * offer more setting possibilities than are actually 
listed here. Refer to the parameter list for additional setting possibilities. 
 
 
 
P0003 = 3
 
User access level * 
 1  Standard: Allows access into most frequently used parameters 
  2  Extended: Allows extended access e.g. to inverter I/O functions 
  3  Expert (For expert use only) 
6.4.1 
Serial Interface (USS) 
 
P2010 =... 
 
USS baud rate 
Sets baud rate for USS communication. 
 
P2011 =... 
 
USS address 
Sets unique address for inverter. 
 
P2012 =... 
 
USS PZD length 
Defines the number of 16-bit words in PZD part of USS telegram. 
 
P2013 =... 
 
USS PKW length 
Defines the number of 16-bit words in PKW part of USS telegram. 
Possible  
Settings: 
 4 
2400 Baud
 5 
4800 Baud
 6 
9600 Baud
 7  19200 Baud
 8  38400 Baud
 9  57600 Baud
 10 
76800  Baud
 11 
93750  Baud
 12  115200  Baud 
6.4.2 
Selection of command source 
 
P0700 =... 
 
 
Selection of  
command source 
Selects digital command source. 
  0  Factory fault setting 
 1  BOP (keypad)  
 2  Terminal 
  4   USS on BOP link 
  5   USS on COM link 
  6  CB on COM link 
P0700 = 2
Sequence control
Setpoint
channel
Motor
control
BOP
USS
BOP link
USS
COM link
Terminals
CB
COM link
 
 
START 
1
 
127
 
2