Technical Data
Model power 
PROTECT B. 750
750 VA / 500 W
PROTECT B. 1000
1000 VA / 700 W
PROTECT B. 1500
1500 VA / 1050 W
PROTECT B. 2000 
2000 VA / 1340 W
PROTECT B. 3000
3000 VA / 2100 W
UPS Input
Rated output voltage
220 / 230 / 240 Vac
Input voltage range
154 / 161 / 168 Vac ± 4%
(wide)
176 / 184 / 192 Vac ± 4%
(standard) until
264 / 276 / 288 Vac ± 4%
Frequency (autom. detection)
50 / 60 Hz ± 5 Hz
> 40 Hz (generator mode)
Curr. consumption (full-load)
PROTECT B. 750
5 A
PROTECT B. 1000
8 A
PROTECT B. 1500
10 A
PROTECT B. 2000
10 A 
PROTECT B. 3000
16 A 
Connection
IEC power connector 
(IEC 320)
USP output
Rated output voltage / 
220 / 230 / 240 Vac 
AVR-technology
Rated output voltage in 
± 5 % 
battery mode
Frequency in battery mode
50 Hz / 60 Hz  ± 0.1 Hz