AEG PROTECT B. 3000 User Manual

Page of 54
17
Recharge time 
3 h (UPS in 
(to 90 % of rated capacity)
standard configuration)
7 h (UPS with 1 add. battery
pack)
12 h (UPS with 2 add. 
battery packs)
18 h (UPS with 3 add. 
battery packs)
24 h (UPS with 4 add. 
battery packs)
Type
Sealed, maintenance free, 
hot swappable (from B.1500)
PROTECT B. 750
12 V / 7 Ah x 2
PROTECT B. 1000
12 V / 9 Ah x 2
PROTECT B. 1500 / B. 1500BP
12 V / 7 Ah x 4
PROTECT B. 2000 / B. 2000BP
12 V / 9 Ah x 4
PROTECT B. 3000 
12 V / 5 Ah x 8
PROTECT B. 3000 BP
12 V / 5 Ah x 8 x 2
Communication
Interfaces
USB and RS232
Additionally from
PROTECT B.1500: 
Communication slot
for i.e. SNMP as well as
input contact for 
emergency shutdown
Shutdown-Software on CD
For all typical operating 
systems, e.g. Windows, 
Linux, Mac, Unix, FreeBSD, 
Novell, Sun
Physical data
Noise (1 m distance)
< 45 dB(A)
Operation temperature range
0°C - 40°C
Humidity
0 - 90% (without condens.)
Installation height
up to 1000 m at rated power