MGE UPS Systems Switched PDU User Manual

Page of 62
   
3. Operations 
 
System Administration 
Creating a location description 
The Set Location command specifies text that appears in the HTML control screen’s Location field. The text is 
also appended to a Welcome to banner that appears when a user successfully logs in serially or through a 
Telnet session. 
If you do not issue this command, or if you issue this command without specifying any text, the control screen ’s 
Location field will be blank and no Welcome to banner will be displayed. 
To create a location description: 
At the Switched PDU: prompt, type 
set location
, followed by a descriptive name of up to 24 alphanumeric and 
other typeable characters (ASCII 32 to 126 decimal - spaces are allowed). Press 
Enter
Omitting any characters after typing ‘set location’ deletes any previously specified text. 
Examples 
The following command specifies Florida HQ as the descriptive location for the control screen and the login 
banner: 
Switched PDU: set location Florida HQ<Enter> 
The following command deletes any previously specified location description: 
Switched PDU: set location<Enter> 
In this case, the control screen’s Location field will be blank, and no welcome banner will be displayed after a 
successful login. 
Displaying system configuration information 
The Show System command displays all system configuration information.  
• Firmware 
version 
• 
NIC module serial number and MAC address 
• 
Hardware revision code and Flash size 
• 
Uptime since last system restart 
• 
System location description 
To display system configuration information: 
At the Switched PDU: prompt, type 
show system
 and press 
Enter
Example 
   System Information 
      F/W Version:   Switched PDU Version 5.3a 
      NIC S/N:       1600001 
      MAC Address:   00-0a-9c-10-00-01 
      H/W Rev Code:  0 
      Flash Size:    1 MB 
      Uptime:        0 days 6 hours 14 minutes 1 second 
      Location:      Florida HQ 
301-0399-4 Rev A. - Page 37