MGE UPS Systems 4000 RT User Manual

Page of 38
34008030EN/AA
 - Page 27
4. Access to measurements and personalisation data
Battery settings  
4.5 Maintenance
  
4.6 Personalisation using external software
  
Function
Factory setting
Options
Comments
Auto Battery Test
Everyweek
No test / everyday / 
everyweek /everymonth
Low Batt Warning
20%
0 to 100%
1% increment
User Batt Settings
UPS reads number of 
battery modules 
connected
From 0 to 40 Ah
5 Ah increment
Deep Disch Protect
Yes
No
Protection against deep discharge.
If disable, MGE UPS SYSTEMS 
warranty will be void
Function
Sub-Function
Option / Display
Comments
Model
Power Module
SN: xxxxxxxxx
SOFT: xxx
NT: xxx
Serial number
Soft version
Technical level
Frame
Alarm History
Read
Description
Date Hour
Alarm xxx
10 alarms can be stored 
automatically
Erase
No / Yes
Manual Batt Test
Manual Battery Test
No / Yes
Led & Buzzer Test
Led & Buzzer Test
No / Yes
Life Cycle Monitoring
LCM
Enable / Disable
Life cycling monitoring alarms
Statistics
Auto Statistics
Statistics
You need to register at 
www.mgeups.com/Icm to get the 
code and get access to free statistics
Custom Statistics
Reset Date ?
Are you sure ?
Operation Limits
Operation Limits
Automatic alarms displayed when 
UPS is operating near the limits
  
  Insert the Solution-Pac CD-ROM in the drive.
  On the first navigation screen, select 
"
Point to Point solution
"
 and follow the instructions on how to install the Personal 
Solution-Pac software.
  Then select 
"
Settings
"
"
Advanced settings
"
 and 
"
UPS settings
"
.
Note that only the Windows versions of the Personal Solution-Pac software offer this possibility.