MGE UPS Systems 4000 RT 用户手册
34008030EN/AA
- Page 27
4. Access to measurements and personalisation data
Battery settings
4.5 Maintenance
4.6 Personalisation using external software
Function
Factory setting
Options
Comments
Auto Battery Test
Everyweek
No test / everyday /
everyweek /everymonth
everyweek /everymonth
Low Batt Warning
20%
0 to 100%
1% increment
User Batt Settings
UPS reads number of
battery modules
connected
battery modules
connected
From 0 to 40 Ah
5 Ah increment
Deep Disch Protect
Yes
No
Protection against deep discharge.
If disable, MGE UPS SYSTEMS
warranty will be void
If disable, MGE UPS SYSTEMS
warranty will be void
Function
Sub-Function
Option / Display
Comments
Model
Power Module
SN: xxxxxxxxx
SOFT: xxx
NT: xxx
SOFT: xxx
NT: xxx
Serial number
Soft version
Technical level
Soft version
Technical level
Frame
Alarm History
Read
Description
Date Hour
Alarm xxx
Date Hour
Alarm xxx
10 alarms can be stored
automatically
automatically
Erase
No / Yes
Manual Batt Test
Manual Battery Test
No / Yes
Led & Buzzer Test
Led & Buzzer Test
No / Yes
Life Cycle Monitoring
LCM
Enable / Disable
Life cycling monitoring alarms
Statistics
Auto Statistics
Statistics
You need to register at
www.mgeups.com/Icm to get the
code and get access to free statistics
www.mgeups.com/Icm to get the
code and get access to free statistics
Custom Statistics
Reset Date ?
Are you sure ?
Are you sure ?
Operation Limits
Operation Limits
Automatic alarms displayed when
UPS is operating near the limits
UPS is operating near the limits
◗
Insert the Solution-Pac CD-ROM in the drive.
◗
On the first navigation screen, select
"
Point to Point solution
"
and follow the instructions on how to install the Personal
Solution-Pac software.
◗
Then select
"
Settings
"
,
"
Advanced settings
"
and
"
UPS settings
"
.
Note that only the Windows versions of the Personal Solution-Pac software offer this possibility.