APC SMC10002U User Manual

Page of 18
7
Smart-UPS C  1000/1500/2000/3000 VA  120/230 Vac  Rack-Mount 2U
LED status indicators
LCD status indicators
Status
LED 
Audible 
Indicator On
Audible Indicator Terminates
Power On 
The UPS is supplying AC
 
power 
to connected equipment.
The On Line/On 
Battery LED 
illuminates green.
None
N/A
On Battery
The UPS is supplying battery 
power from the internal battery.
The On Line/On 
Battery LED 
illuminates amber.
The UPS beeps 
4 times every 
30 seconds.
The beeping stops when AC power is 
restored or the 
MUTE
 button is pressed 
for two seconds.
System Fault
The UPS detects an internal 
system fault. 
System Fault 
LED illuminates 
red. 
Constant tone
The alarm stops when the 
POWER
 
ON
/
OFF
 button is pressed for two 
seconds. This creates a Fault Reset.
Site Wiring Fault
A building wiring fault has 
occurred. Do not operate the UPS. 
Contact a qualified electrician to 
correct the building wiring fault.
Site Wiring Fault 
LED flashes red
None
N/A
Status
LCD Icon
Audible Alarms
Audible Alarm Terminates
On Battery
The UPS is supplying 
battery power to the 
connected equipment.
Beeps 4 times every 30 
seconds.
The beeping stops when AC 
power is restored or the UPS 
is turned off.
AC Power Overload
An overload condition has 
occurred while the UPS is 
operating on AC power.
Constant tone
The alarm stops when 
nonessential equipment is 
disconnected from the outlets 
or the UPS is turned off
Battery Power Overload 
An overload condition has 
occurred while the UPS is 
operating on battery power.
Constant tone
The alarm stops when 
nonessential equipment is 
disconnected from the outlets 
or the UPS is turned off.
Low Battery
The UPS is supplying 
battery power to the 
connected equipment and 
the battery is near a total 
discharge state.
Continuous beeping
The beeping stops when AC 
power is restored or the UPS 
is turned off.
Battery Fault
The UPS is operating on AC 
power. The battery does not 
provide expected backup.
The UPS will beep twice to 
indicate the battery is 
disconnected.
The UPS will beep 
continuously for one minute 
every five hours to indicate 
that the battery should be 
replaced.
Verify that the battery is 
securely connected.
The battery is nearing the 
end of its service life and 
should be replaced.
System Fault
The UPS has experienced an 
internal fault.
120 Vac models
230 Vac models
N/A
Identify the fault message on 
the display and refer to 
System Faults in this 
manual.