Specifications
Input conductors
This product is rated 200 A. It should be supplied with a circuit breaker
with a maximum rating of 200 A.
with a maximum rating of 200 A.
For North America, if supplied by a 200 A circuit breaker, it is
recommended that conductors are sized in accordance with Table 3.
recommended that conductors are sized in accordance with Table 3.
For countries outside of North America, if supplied by a 200 A circuit
breaker, it is recommended that conductors are sized in accordance with
Table 4.
breaker, it is recommended that conductors are sized in accordance with
Table 4.
Note: Input conductors are to be torqued to 31.1 Nm
(275 lb-in) using a 8 mm (5/16 in) Allen (hexagonal) wrench.
(275 lb-in) using a 8 mm (5/16 in) Allen (hexagonal) wrench.
Table 1
Table 2
Table 3
Notes
CCC = Current-Carrying Conductors
AWG = American Wire Gauge
kcmils = MCM = Thousands of Circular Mils
Ø = Phase conductor
N = Neutral conductor
G = Ground (Equipment Grounding) conductor
(2) = two conductors per terminal
CCC = Current-Carrying Conductors
AWG = American Wire Gauge
kcmils = MCM = Thousands of Circular Mils
Ø = Phase conductor
N = Neutral conductor
G = Ground (Equipment Grounding) conductor
(2) = two conductors per terminal
Table 4
Notes
Ø = Phase conductor
N = Neutral conductor
PE = Protective Earth conductor
PVC = Polyvinyl-chloride
XLPE = Cross-linked polyethylene
EPR = Ethylene propylene rubber
Ø = Phase conductor
N = Neutral conductor
PE = Protective Earth conductor
PVC = Polyvinyl-chloride
XLPE = Cross-linked polyethylene
EPR = Ethylene propylene rubber
AC Input
Nominal voltage
400 V 3 PH
208 V 3 PH
208 V 3 PH
Frequency
47-63 Hz
Voltage configuration
3 W + N + PE
Maximum upstream circuit breaker
200 A
Maximum continuous current
160 A
Maximum continuous current with
100% rated circuit breaker
100% rated circuit breaker
200A
Maximum main input conductor size
250 mcm
AC Output
Nominal voltage
230 V/400 V 3 PH
120 V/208 V 3PH
120 V/208 V 3PH
Maximum continuous current
200 A
Voltage configuration
3 W + N + PE or 3 x (1 W + N + PE),
based on attached APC Power
Distribution Modules
based on attached APC Power
Distribution Modules
Full load rating
138 kW @ 400 V 3PH
72 kW @ 208 V 3 PH
72 kW @ 208 V 3 PH
Output power cable connections
Various, based on attached APC Power
Distribution Modules
Distribution Modules
Output power cable lengths
Various, based on attached APC Power
Distribution Modules
Distribution Modules
Maximum APC Power Distribution
Modules
Modules
6
Maximum power distribution poles
18
200 A, 75°C Conductors
Wiring System
Copper
Aluminum
3 CCC, 30°C Ambient Ø&N = 3/0 AWG
G = 6 AWG
Ø&N = 4/0 AWG
G = 4 AWG
G = 4 AWG
4 CCC, 30°C Ambient Ø&N = 4/0 AWG
G = 6 AWG
Ø&N = (2) 1/0 AWG
G = (2) 4 AWG
G = (2) 4 AWG
200 A, Conductors
Install.
Method
Copper, PVC
Insulation,
Insulation,
30°C Ambient
Copper, XLPE
or EPR
Insulation,
Insulation,
30°C Ambient
Aluminum,
PVC Insulation,
PVC Insulation,
30°C Ambient
Aluminum,
XLPE or ERP
Insulation,
Insulation,
30°C Ambient
B1
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
Ø&N = 70 mm²
PE = 35 mm²
PE = 35 mm²
Ø&N = 150 mm²
PE = 95 mm²
PE = 95 mm²
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
B2
Ø&N = 120 mm²
PE = 70 mm²
PE = 70 mm²
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
Ø&N = 240 mm²
PE = 120 mm²
PE = 120 mm²
Ø&N = 120 mm²
PE = 70 mm²
PE = 70 mm²
C
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
Ø&N = 70 mm²
PE = 35 mm²
PE = 35 mm²
Ø&N = 150 mm²
PE = 95 mm²
PE = 95 mm²
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
E
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
Ø&N = 70 mm²
PE = 35 mm²
PE = 35 mm²
Ø&N = 120 mm²
PE = 70 mm²
PE = 70 mm²
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
F
Ø&N = 70 mm²
PE = 35 mm²
PE = 35 mm²
Ø&N = 50 mm²
PE = 25 mm²
PE = 25 mm²
Ø&N = 95 mm²
PE = 50 mm²
PE = 50 mm²
Ø&N = 70 mm²
PE = 35 mm²