2.6 Connection of power cables in a single UPS unit
 Interconnecting the cabinet earths
UPS units with common normal and Bypass AC inputs 
UPS units with separate normal and Bypass AC inputs 
Frequency converter 
  
All the cabinet earths must be interconnected: external Bypass cabinet, external battery cabinet, etc.
    
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing-plate 
connectors (17) and (18).
2 - Connect the four conductors of the Normal AC source to terminal block 
(15).
3 - Connect the three phases of the Normal AC input (16) with the three 
phases of the Bypass AC input (15).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Tie the cables down to the frame.
6 - Put the cover back in place (see section 1.2).
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing-plate 
connectors (17) and (18).
2 - Connect the three phases of the Normal AC source to terminal block 
(16).
3 - Connect the four conductors of the Bypass AC source to terminal block 
(15).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Tie the cables down to the frame.
6 - Put the cover back in place (see section 1.2).
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing plate.
2 - Connect the neutral conductor of the Normal AC source to the neutral 
terminal on terminal block (15).
3 - Connect the three phases of the Normal AC source to terminal block 
(16).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Connect the neutral on terminal block (15) with the neutral of the 
supplied loads on terminal block (14).
6 - Tie the cables down to the frame.
7 - Put the cover back in place (see section 1.2).
  
Do not connect anything to the three phases on the Bypass AC 
source terminal block 
 (15).
N L1 L2 L3
14
16
15
N L1 L2 L3
L1 L2 L3
17
18
370 mm
370 mm
N L1 L2 L3
14
16
15
N L1 L2 L3
L1 L2 L3
17
18
370 mm
N L1 L2 L3
14
16
15
N L1 L2 L3
L1 L2 L3
17
18