2. Installation
2.8 Connection of power cables for parallel UPS units
Equipotential bonding between parallel-connected units
Connect the exposed conductive parts (ECP) of the parallel-connected UPS units using an additional earthing cable (not 
supplied) with the following characteristics:
- size equivalent to that of the supply cables,
- as short as possible.
Connection of earth cable and tying of cables 
Connections must be made according to the diagram below:   
 
N L1 L2 L3
N L1 L2 L3
L1 L2 L3
N L1 L2 L3
N L1 L2 L3
L1 L2 L3
N L1 L2 L3
N L1 L2 L3
L1 L2 L3
Main earth
Main earth
Additional equipotential
bonding between units.
UPS 1
UPS 3
UPS 2