APC PDPM150G6F User Manual

Page of 28
150/175kw Modular PDU Installation
8
Bottom entry installation
Note: The sidecar is required for undefloor wiring into the PDU. The Sidecar does not contain a switch 
or circuit breaker so a readily accessible disconnect device shall be incorporated external to the 
equipment. 
1 Remove the dedicated cover plate. Drill holes 
in the plate for conduits and re-install the 
plate with the conduits installed. Route the 
conductors (input conductors in single utility 
systems or bypass conductors in dual utility 
systems) through the bottom of the Side Car.
2 Connect the input/bypass conductors to the 
L1, L2, L3, EGC, and GEC terminals and 
torque to specifications on label.
Sidecar Model
PDU Model
PDPM150SC
PDPM150G6F
PDPM150L6F
PDPM100SC
PDPM175G6H
pdx0878a