APC PDUM160H-B User Manual
Operation: Operation Procedures
10
Symmetra PX 160 kW 400 V Operation
990-3015-001
Set the Q2 switch on the PDU-XR to the OFF
position.
Turn the UPS off using the display.
Set the Q1 switch on the PDU-XR to the OFF
position.
Set the Q5 switch on the PDU-XR to the OFF
position.
Set the
UPS
S
YSTEM
E
NABLE
switch to the OFF
position.
Set the
DC D
ISCONNECT
switch on all of the XR Battery enclosures and the PDU-XR to the OFF
position.
Press
Press
Press
Press
UPS
Alarms
Power Dist
Switch Gear
Environment
Switch Gear
Environment
Log
Admin
Help
Admin
Help
UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
Reboot UPS
UPS into Bypass
UPS to Sleep
Notify PowerChute?
Cancel
Yes, Notify Servers
No, Don’t Notify
Cancel
Yes, Notify Servers
No, Don’t Notify
Turn UPS Off With
Server Notification?
>NO, ABORT
>YES, Turn UPS Off
Server Notification?
>NO, ABORT
>YES, Turn UPS Off
Turning UPS off,
please wait...
please wait...