990-3015-001
Symmetra PX 160 kW 400 V Operation 
11
How to return to normal operation 
Set the 
DC D
ISCONNECT
 
switch on all of the XR Battery enclosures and the PDU-XR to the ON 
position.
Set the Q1 switch on the PDU-XR or external maintenance bypass panel to the ON position. 
Set the Q5 switch
 
on the PDU-XR or external maintenance bypass panel to the ON position. 
Set the 
S
YSTEM
 E
NABLE
 switch on the UPS to the ON position.
Note: Wait approximately 30 seconds for system to start. 
Using the display interface, select the following: 
Press
Press
Press
 Press
UPS
Alarms
Power Dist
Switch Gear
Environment
Log
Admin
Help
UPS Control
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS On
UPS On Into Bypass
UPS Load is ON.