Magnum VS –48 Vdc User’s Manual 
                                     
  Page 31 
PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
Settings in BOLD) 
Battery Temperature 
[STATUS/BATTERY/ 
PARAMETERS] 
[
状态 / 电池 /参数] 
Battery temperature measured by the 
system controller at the optional battery 
temperature sensor probe. 
Battery Temperature 
Status Only 
Date Setup 
[SETUP/SYSTEM/TIME/DATE] 
[
设置 / 系统 / 时/日] 
System date stored in the controller.  
Used as a date stamp in the event log. 
Current DATE 
Date Status 
[STATUS/SYSTEM/Time/Date] 
[
状态 / 系统 / 时/日] 
Displays the current controller date.  
Date Status Only 
Equalize Automatically On/Off 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
METHOD/AUTO] 
[
设置 / 电池 /电压 / 
均充 / 模式 / 自动]
 
Applies an overcharge to the battery to 
equalize the specific gravity of a battery.  
Auto equalization is initiated when the 
controller determines that the batteries 
have been discharged a set percentage 
of their capacity or the batteries have 
been on discharge for a set duration.  
Use this screen to turn auto equalization 
on. 
ON, OFF 
Equalize Automatically on AC 
Fail 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
METHOD/AUTO/AC 
FAIL/ON/OFF] 
[
设置 / 电池 /电压 / 
均充 / 模式 / 自动 
/自动] 
 
Sets the time the ac input power has to 
be off before equalization occurs. 
15 MINUTES – 360 
MINUTES, 15 MINUTES 
Equalize Automatically on 
Battery Discharge 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
METHOD/AUTO/DISCHARGE] 
[
设置 / 电池 /电压 / 
均充 / 模式 / 自动 / 
交流故障]
 
Sets the percent of battery discharge 
before equalization occurs.  Percent 
Discharge = Discharged ampere-hours / 
Battery Capacity ampere-hours 
5% - 50%, 30 %