APC VS 100 User Manual

Page of 65
Magnum VS –48 Vdc User’s Manual 
                                     
  Page 32 
PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
Settings in BOLD) 
Equalization Duration 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
DURATION] 
[
设置
 / 电池 / 电压 / 
均充 / 均充时间] 
This setting defines the number of hours 
the batteries will be equalized in all 
methods of equalization.  During the 
initial stage of equalization the batteries 
will have to be increased to the 
equalization voltage.  Once the battery 
voltage and current meet equalization 
parameters, the equalization duration 
timer will start.  
 00 HOURS- 24 HOURS, 
0 HOURS 
Equalize Manually 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
METHOD/MANUAL] 
[
设置 / 电池 /电压 / 
均充 / 模式 /手动]
 
Applies an overcharge to the battery to 
equalize the specific gravity of a battery.  
Manual equalization is a one-time 
equalization process.  The operator turns 
on manual equalization each time he 
wishes an unscheduled equalization to 
occur.  To abort an automatic or periodic 
equalization in progress, turn manual 
equalization ON and then OFF.     
ON, OFF 
Equalize Periodically 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
METHOD/PERIODIC] 
[
设置 / 电池 /电压 / 
均充 / 模式 /周期]
 
Applies an overcharge to the battery to 
equalize the specific gravity of a battery.  
Periodic equalization is equalization after 
a set number of days.   
ON, OFF; 
0-180 Days, 180 Days 
Equalization Voltage 
[SETUP/BATTERY/ 
VOLTAGE/EQUALIZATION/ 
VOLTAGE] 
[
设置 / 电池 / 电压 / 
均充 / 电压] 
The overcharge voltage that will be 
applied to the battery 
-56.5 V - -48.0 V, -56.0 V 
Language Selection 
The screen will revert to the language 
selection screen after a reset.  Choices 
are English and Chinese. 
 
Pin Entry 
[SETUP] 
[
设置] 
Enter PIN to access setup menus.  
Entering setup brings you to the PIN 
entry screen.  In-activity for two minutes 
will de-activate system access. 
0000 – 9999, 2222 
PIN Setup 
[SETUP/SYSTEM/SET PIN] 
[
设置 / 系统 / 码设置] 
Change PIN that the user will use to log 
on to the system.  If you change the PIN, 
Do Not Forget It. 
0000 – 9999, 2222 
Rectifier Current Limit Status  
{Status Only} 
[STATUS/RECT] 
状态 / 模块] 
A display of the current limit alarm for the 
individual rectifier.  Scroll up or down to 
select individual rectifiers. 
Rectifier Current Limit 
Status Only