Magnum VS –48 Vdc User’s Manual 
                                     
  Page 39 
PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
settings in BOLD) 
Battery Max Recharge 
{Status Only} 
[System/DC Parameters] 
This is just a convenient place to view 
the Battery Max Recharge Current 
parameter.  Go to Batteries/Parameters 
to change setting. 
Status Only 
Battery Maximum Recharge 
Current 
[Batteries/Parameters] 
One of three parameters that control the 
dc output voltage.  If Battery Current 
surpasses the Maximum Battery 
Recharge Current, the dc output voltage 
will be reduced (the system limits the 
charging current to this programmable 
value). 
0 – 10,000 A, 10 A 
Battery Temperature 
[System/DC Parameters] 
Battery temperature measured by the 
system controller at the optional battery 
temperature sensor probe. 
Status Only 
Battery Temperature 
Compensation High Knee  
[Batteries/Parameters] 
The temperature compensation high 
knee is the point where there is no 
additional battery voltage compensation 
for further increases in temperature. 
0 °C – 100 °C, 40.0 °C 
Battery Temperature 
Compensation Low Knee  
[Batteries/Parameters] 
The temperature compensation low knee 
is the point where there is no additional 
battery voltage compensation for further 
decreases in temperature. 
-100 °C – 100 °C, 0.0 °C 
Battery Temperature 
Compensation Method  
[Batteries/Parameters] 
One of three parameters that control the 
dc output voltage.  Activate “ON” or de-
activate “OFF” battery temperature 
compensation.  
ON, OFF 
Battery Temperature 
Compensation Temperature 
Coefficient 
[Batteries/Parameters] 
Temperature compensation coefficient 
between low knee and high knee in 
mV/cell/°C.  (Compensation equals zero 
at 25°C.) 
-4.99 mV – 0 mV,  
-3.00mV 
Circuit Breaker 1 Alias 
[Distribution/Breakers] 
• 
• 
  
Circuit Breaker 4 Alias  
[Distribution/Breakers] 
 
An alternate name (alias) can be 
assigned to Circuit Breaker 1 if desired. 
This feature is supported by the standard 
SNMP card monitor, but is not supported 
by this dc system. 
Circuit Breaker 1  
 
• 
• 
  
Circuit Breaker 4  
 
 
Circuit Breaker 1 Tripped  
[Distribution/Breakers] 
• 
• 
• 
Circuit Breaker 4 Tripped  
[Distribution/Breakers] 
Defines the output relay that is energized 
when Circuit Breaker 1 is tripped. 
• 
• 
• 
Defines the output relay that is energized 
when Circuit Breaker 4 is tripped. 
Ignore, Minor, Major 
Output Relay 1-6 
• 
• 
• 
Ignore, Minor, Major 
Output Relay 1-6 
Circuit Breaker 5-72 is not 
used in this system. 
Communications Fail 
 
Defines the output relay that is energized 
if the System stops communicating with 
the rectifiers.  This feature is supported 
by the standard SNMP card monitor, but 
is not supported by this dc system. 
Ignore, Minor, Major 
Output Relay 1-6•