APC VS 100 User Manual

Page of 65
Magnum VS –48 Vdc User’s Manual 
                                     
  Page 40 
PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
settings in BOLD) 
Current Limit Alarm Status 
{Status Only} 
[Power Modules/Rectifiers] 
The status will be “ON” if the rectifier has 
been forced into its current limited mode.  
Status Only 
Date  
[System/Date & Time] 
Internal network management card 
calendar date.  Used as a date stamp in 
the web card event log. 
Current Date 
Description 1 
 [System/DC Parameters] 
Power plant identification - first line. 
 
Description 2 
[System/DC Parameters] 
Power plant identification - second line. 
Magnum VS 
This is not user edit-able. 
Description 3  
 [System/DC Parameters] 
Power plant identification - third line. 
Power System 
This is not user edit-able. 
Fail Safe  
[Power Modules/Rectifiers] 
If the rectifiers fail to communicate with 
the system, the rectifiers will output this 
pre-defined voltage.   
This feature is supported 
by the standard SNMP 
card monitor, but is not 
supported by this dc 
system. 
FUSE 1 Alias  
[Distribution/Fuses] 
• 
  
 
FUSE 1 Alias  
[Distribution/Fuses] 
An alternate name (alias) can be 
assigned to Fuse 1 if desired.  This 
feature is supported by the standard 
SNMP card monitor, but is not supported 
by this dc system. 
FUSE 1 
 
• 
  
• 
FUSE 16 
FUSE 1 Blown  
[Distribution/Fuses] 
• 
• 
• 
FUSE 4 Blown  
[Distribution/Fuses] 
Defines the output relay that is energized 
when F1-4 is blown. 
• 
• 
• 
Defines the output relay that is energized 
when F13-16 is blown. 
Ignore, Minor, Major 
Output Relay 1-6 
• 
• 
• 
Ignore, Minor, Major 
Output Relay 1-6 
Fuse 5-16 is not used in 
this system 
Hardware Battery Current 
Alarm 
[Batteries Parameters] 
Defines the output relay that is energized 
if there is a hardware failure in the 
battery current monitoring function.  This 
feature is supported by the standard 
SNMP card monitor, but is not supported 
by this dc system. 
Ignore, Minor, Major 
Output Relay 1-6 
 
Hardware Battery Temperature 
Alarm 
[Batteries Parameters] 
Defines the output relay that is energized 
if there is a hardware failure in the 
battery temperature monitoring function.  
Program to Ignore if no battery 
temperature probe is connected to J410. 
Ignore, Minor, Major 
Output Relay 1-6 
Hardware LVD Alarm 
[Batteries/LVD] 
Defines the output relay that is energized 
if there is a conflict between the 
commanded and sensed positions of the 
LVD contactor.  This feature is supported 
by the standard SNMP card monitor, but 
is not supported by this dc system. 
Ignore, Minor, Major 
Output Relay 1-6