  Page 43 
PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
settings in BOLD) 
Output Relay 1 Alias  
 [System/Out-Rly/Alias] 
• 
• 
• 
Output Relay 6 Alias   
[System/Out-Rly/Alias] 
An alternate name (alias) can be 
assigned to Output Relay 1 if desired. 
 
• 
• 
An alternate name (alias) can be 
assigned to Output Relay 6 if desired. 
Output Relay 1  
  
• 
• 
• 
Output Relay 6  
 
Output Relay 1 Delay  
[I/O/Output] 
• 
• 
• 
Output Relay 6 Delay  
[I/O/Output] 
Delay between sensing of the alarm 
condition and activation of the mapped 
relay.  An alarm condition must exist for 
longer than the delay to be activated.   
0.00 seconds – 600.00 
seconds, 0.00 seconds 
Rectifier 1-of-N Alarm 
[Power Modules/Rectifiers] 
Defines the output relay that is energized 
if Rectifier Fail 1-of-N alarm occurs.  This 
is a special rectifier alarm group that 
signifies that one rectifier has at least 
one alarm condition. 
Ignore, Minor, Major 
Output Relay 1-6 
Rectifier 2-of-N Alarm 
[Power Modules/Rectifiers] 
Defines the output relay that is energized 
if Rectifier Fail 2-of-N alarm occurs This 
is a special rectifier alarm group that 
signifies that more than one rectifier has 
at least one alarm condition. 
Ignore, Minor, Major 
Output Relay 1-6 
Rectifier Configuration Alarm 
[Power Modules/Rectifiers] 
Defines the output relay that is that is 
energized a rectifier is added to any 
empty slot after the dc system is 
powered up or configured.  This feature 
is supported by the standard SNMP card 
monitor, but is not supported by this dc 
system. 
Ignore, Minor, Major 
Output Relay 1-6, n of N 
Rectifier Current Limit Alarm 
[Power Modules/Rectifiers] 
Defines the output relay that is energized 
or special rectifier alarm group n of N that 
occurs when a rectifier has been forced 
into the current limited mode. 
Ignore, Minor, Major 
Output Relay 1-6, n of N 
Rectifier Current Output Status  
{Status Only} 
[Power Modules/Rectifiers] 
A display of the dc output current for the 
individual rectifier.   
Status Only 
Rectifier Description 
{Status Only} 
[Power Modules/Rectifiers] 
Displays the model number of the 
installed rectifier.   
Status Only 
Rectifier Diagnostic Alarm 
[Power Modules/Rectifiers] 
This feature is not needed in this 
particular configuration. 
Ignore, Minor, Major 
Output Relay 1-6, n of N 
Rectifier Fan Fail Alarm  
[Power Modules/Rectifiers] 
Defines the output relay that is energized 
or special rectifier alarm group n of N that 
occurs when a rectifier fan has failed. 
Ignore, Minor, Major 
Output Relay 1-6
n of N 
Rectifier Fan Fail Alarm Status 
{Status Only} 
[Power Modules/Rectifiers] 
The status will be “ON” if the rectifier fan 
has failed.   
Status Only