PARAMETER NAME/ 
[MENU LOCATION] 
DESCRIPTION SETTINGS 
(Default 
settings in BOLD) 
Low Temperature Threshold  
[System/DC Parameters] 
System Temperature is ambient 
temperature measured inside the 
controller.  An alarm will be reported if 
temperature is lower than the 
temperature entered.  Not the same as 
battery temperature threshold. 
-100 °C  – 100 °C, 0.0 °C 
Low Voltage Alarm 
[Power Modules/Rectifiers] 
Defines the output relay that is energized 
if the System Voltage is below the 
System Low Voltage threshold.  Not the 
same as battery voltage alarm. 
Ignore, Minor, Major 
Output Relay 1-6 
Low Voltage Threshold 
[Power Modules/Rectifiers] 
System Voltage is bus voltage measured 
by the controller.  An alarm will be 
reported if voltage is lower than the 
voltage entered.  Not the same as battery 
voltage threshold. 
-60 V – -40 V, -50.00 V 
LVD 1 Option 
[Batteries/LVD] 
If the unit has an LVD, but it is disabled, 
the controller will not disconnect the LVD. 
Enable, Disable 
LVD 1 Reset 
[Batteries/LVD] 
LVD Reset (reconnect) threshold voltage.  -56 V – -40 V, -50.00 V 
LVD 1 Trip 
[Batteries/LVD] 
LVD Trip (disconnect) threshold voltage. 
-56 V – -40 V, -42.00 V 
LVD 2 Option 
[Batteries/LVD] 
Not available on this system. 
Disable 
LVD 2 Reset 
[Batteries/LVD] 
Not available on this system. 
0.00 V 
LVD 2 Trip 
[Batteries/LVD] 
Not available on this system. 
0.00 V 
LVD Alarm  
[Batteries/LVD] 
Defines the output relay that is energized 
when the controller opens the LVD.  If 
unit has a battery LVD, no power will be 
available to turn on any Output Relays. 
Ignore, Minor, Major 
Output Relay 1-6 
Output Relay 1 Alarm 
[I/O/Output] 
 
Output Relay 1 Alarm can be “mapped” 
to activate other output relays (“Ignore” 
activates no additional relays).   
Ignore, Minor, Major 
Output Relay 1-6 
 
 
Output Relay 2 Alarm 
[I/O/Output] 
 
• 
• 
• 
Output Relay 6 Alarm 
[I/O/Output] 
Output Relay 2-6 Alarm can be “mapped” 
to activate other output relays (“Ignore” 
activates no additional relays).  Alarms 
that are mapped to output relay 2-6 are 
not supported by hardware.  The network 
management card supports programming 
these relays.  These relays can be 
mapped to the hardware relays minor 
and major. 
Ignore, Minor, Major 
Output Relay 1-6 
 
 
• 
• 
• 
Ignore
, Minor, Major 
Output Relay 1-6