APC VS 100 User Manual
Magnum VS –48 Vdc User’s Manual
Page 42
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS
(Default
settings in BOLD)
Low Temperature Threshold
[System/DC Parameters]
[System/DC Parameters]
System Temperature is ambient
temperature measured inside the
controller. An alarm will be reported if
temperature is lower than the
temperature entered. Not the same as
battery temperature threshold.
temperature measured inside the
controller. An alarm will be reported if
temperature is lower than the
temperature entered. Not the same as
battery temperature threshold.
-100 °C – 100 °C, 0.0 °C
Low Voltage Alarm
[Power Modules/Rectifiers]
[Power Modules/Rectifiers]
Defines the output relay that is energized
if the System Voltage is below the
System Low Voltage threshold. Not the
same as battery voltage alarm.
if the System Voltage is below the
System Low Voltage threshold. Not the
same as battery voltage alarm.
Ignore, Minor, Major
Output Relay 1-6
Output Relay 1-6
Low Voltage Threshold
[Power Modules/Rectifiers]
[Power Modules/Rectifiers]
System Voltage is bus voltage measured
by the controller. An alarm will be
reported if voltage is lower than the
voltage entered. Not the same as battery
voltage threshold.
by the controller. An alarm will be
reported if voltage is lower than the
voltage entered. Not the same as battery
voltage threshold.
-60 V – -40 V, -50.00 V
LVD 1 Option
[Batteries/LVD]
[Batteries/LVD]
If the unit has an LVD, but it is disabled,
the controller will not disconnect the LVD.
the controller will not disconnect the LVD.
Enable, Disable
LVD 1 Reset
[Batteries/LVD]
[Batteries/LVD]
LVD Reset (reconnect) threshold voltage. -56 V – -40 V, -50.00 V
LVD 1 Trip
[Batteries/LVD]
[Batteries/LVD]
LVD Trip (disconnect) threshold voltage.
-56 V – -40 V, -42.00 V
LVD 2 Option
[Batteries/LVD]
[Batteries/LVD]
Not available on this system.
Disable
LVD 2 Reset
[Batteries/LVD]
[Batteries/LVD]
Not available on this system.
0.00 V
LVD 2 Trip
[Batteries/LVD]
[Batteries/LVD]
Not available on this system.
0.00 V
LVD Alarm
[Batteries/LVD]
[Batteries/LVD]
Defines the output relay that is energized
when the controller opens the LVD. If
unit has a battery LVD, no power will be
available to turn on any Output Relays.
when the controller opens the LVD. If
unit has a battery LVD, no power will be
available to turn on any Output Relays.
Ignore, Minor, Major
Output Relay 1-6
Output Relay 1-6
Output Relay 1 Alarm
[I/O/Output]
[I/O/Output]
Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).
to activate other output relays (“Ignore”
activates no additional relays).
Ignore, Minor, Major
Output Relay 1-6
Output Relay 1-6
Output Relay 2 Alarm
[I/O/Output]
•
•
•
Output Relay 6 Alarm
[I/O/Output]
[I/O/Output]
•
•
•
Output Relay 6 Alarm
[I/O/Output]
Output Relay 2-6 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays). Alarms
that are mapped to output relay 2-6 are
not supported by hardware. The network
management card supports programming
these relays. These relays can be
mapped to the hardware relays minor
and major.
to activate other output relays (“Ignore”
activates no additional relays). Alarms
that are mapped to output relay 2-6 are
not supported by hardware. The network
management card supports programming
these relays. These relays can be
mapped to the hardware relays minor
and major.
Ignore, Minor, Major
Output Relay 1-6
•
•
•
Ignore, Minor, Major
Output Relay 1-6
Output Relay 1-6
•
•
•
Ignore, Minor, Major
Output Relay 1-6