APC VS 100 User Manual
Magnum VS –48 Vdc User’s Manual
Page 51
8 Alarm
Summary
ALARM/
[MENU LOCATION]
DESCRIPTION DEFAULT
SETTINGS
Battery Discharge Alarm
[Batteries/Parameters]
[Batteries/Parameters]
The battery discharge current exceeds
the programmed battery discharge
threshold.
the programmed battery discharge
threshold.
Minor
Battery High Temp Alm
[Batteries/Parameters]
[Batteries/Parameters]
The battery temperature exceeds the
Battery High Temperature threshold.
Battery High Temperature threshold.
Minor
Battery Low Temp Alm
[Batteries/Parameters]
[Batteries/Parameters]
The Battery Temperature is below the
battery Low Temperature threshold.
battery Low Temperature threshold.
Minor
Battery LV Alm
[Batteries/Parameters]
[Batteries/Parameters]
The dc output voltage is below the
battery low voltage threshold.
battery low voltage threshold.
Major
Circuit Breaker Alm 1
[Distribution/Breakers]
[Distribution/Breakers]
The top Circuit Breaker in the top shelf is
tripped.
tripped.
Major
Circuit Breaker Alm 2
[Distribution/Breakers]
[Distribution/Breakers]
The bottom Circuit Breaker in the top
shelf is tripped
shelf is tripped
Major
Circuit Breaker Alm 3
[Distribution/Breakers]
[Distribution/Breakers]
The top Circuit Breaker in the bottom
shelf is tripped.
shelf is tripped.
Major
Circuit Breaker Alm 4
[Distribution/Breakers]
[Distribution/Breakers]
The bottom Circuit Breaker in the bottom
shelf is tripped
shelf is tripped
Major
FUSE Alm 1
[Distribution/Fuses]
[Distribution/Fuses]
Any of Fuse 1 through 4 is blown.
Major
FUSE Alm 2
[Distribution/Fuses]
[Distribution/Fuses]
Any of Fuse 5 through 8 is blown.
Major
FUSE Alm 3
[Distribution/Fuses]
[Distribution/Fuses]
Any of Fuse 9 through 12 is blown.
Major
FUSE Alm 4
[Distribution/Fuses]
[Distribution/Fuses]
Any of Fuse 13 through 16 is blown.
Major
Hardware Batt Temp Alm
[Batteries Parameters]
[Batteries Parameters]
There is a hardware failure in the battery
temperature monitoring function.
temperature monitoring function.
Minor
Hardware Sys Volt Alm
[Power Modules/Rectifiers]
[Power Modules/Rectifiers]
There is a hardware failure in the system
voltage monitoring function.
voltage monitoring function.
Minor
Hardware Sys Temp Alm
[System/DC Parameters]
[System/DC Parameters]
There is a hardware failure in the system
temperature monitoring function.
temperature monitoring function.
Minor.
System HT Alm
[System/DC Parameters]
[System/DC Parameters]
The System Temperature exceeds the
system high temperature threshold. Not
the same as battery temperature alarm.
system high temperature threshold. Not
the same as battery temperature alarm.
Minor
System HV Alm
[Power Modules/Rectifiers]
[Power Modules/Rectifiers]
The System Voltage is above the System
High Voltage threshold. Not the same as
battery high voltage alarm.
High Voltage threshold. Not the same as
battery high voltage alarm.
Minor
Input Relay 1
[I/O/Input]
•
•
•
Input Relay 4
[I/O/Input]
[I/O/Input]
•
•
•
Input Relay 4
[I/O/Input]
An external contact closure at the Input
Relay 1 connection.
•
•
•
An external contact opening at the Input
Relay 4 connection.
Relay 1 connection.
•
•
•
An external contact opening at the Input
Relay 4 connection.
Ignore
•
•
•
Ignore
•
•
•
Ignore