APC VS 100 User Manual

Page of 65
Magnum VS –48 Vdc User’s Manual 
 
Page 53 
9 Specifications 
 
The overall system specifications can vary, depending upon the number of rectifier modules.  
Note that some specification items are provided on a “per rectifier” basis and must be combined 
or totaled for a given system configuration. 
 
9.1.  AC Input  
 
TWF0500H54B Rectifier 
 
Input Voltage Range 
85 – 264 Vac 
AC Frequency Range 
47 – 63 Hz 
Apparent Power Factor 
99% Typical, 98% Minimum 
Input Current (per Rectifier) 
5.5 A @ 115Vac 
3.7 A @ 230Vac 
Turn on Time  
2 Seconds 
 
Magnum VS 50 Power System 
 
Input Voltage Range 
85 – 264 Vac 
AC Frequency Range 
47 – 63 Hz 
Apparent Power Factor 
99% Typical, 98% Minimum 
Input Current 
27.5 A @ 115 Vac 
18.5 A @ 230 Vac