104   Appendix A:  NT5C10BF-1 and NT5C10BP 
UM5C06B / C ( 169-2071-500 )   P0711722   Standard 10.00   May 2001 
General requirements 
Power shelf size 
The NT5C10BF-1 and NT5C10BP power shelves are designed specifically 
for the FTIP/FTOP application. They measure 17.0 inches W x 7.0 inches H 
x 12.0 inches D. They provide housing for up to three MPR25EX 
(NT5C06BB) SMRs (FTOP application), or two MPR15E (NT5C06CB/CD) 
SMRs plus one 50 A LVD module (NT6C13FA) (FTIP application). The 
middle rectifier is wired as Standby. 
Shelf labeling 
The following component and connection positions are labeled on the 
power shelf: 
a)  Front (left to right): 
- MAIN1 
- STANDBY 
- MAIN2/LVD 
b)  Rear (right to left): 
Signal Connections: 
- RC- 
TB1-1 
- RG+ 
TB1-2 
- J1 
TB1-3 
- J2 
TB1-4 
- RFA 
TB1-5 
- NSR 
TB1-6 
Power Connections: 
- RTNA 
TB2-1 
- -48V A 
TB2-2 
Note:
 
The Standby rectifier HVSD should be adjusted 0.5 
higher than the main rectifier(s) and its float voltage 
should be adjusted 0.1 volts lower than the main 
rectifier(s).