106   Appendix B:  NT5C10CO shelf 
UM5C06B / C ( 169-2071-500 )   P0711722   Standard 10.00   May 2001 
Technical specifications 
 
 
 
WARNING 
The power shelf must be connected to 120 V AC and a 
20-ampere circuit. The AC receptacle must be rated 20 
amperes and wired with #12 AWG. Non-conformance to 
these requirement may cause the AC breaker/fuse at the 
AC distribution cabinet to open, under certain operational 
conditions, resulting in loss of power for both rectifiers. 
Input AC: 
120 V AC/18 A 
Power system maximum load: 
6 A typical to 10 A maximum. 
Battery charging current: 
7 to 11 A, depending on power system 
load. 
Maximum battery reserve: 
120 AH (based on 8 hours). 
Delayed Start delay: 
Two positions; 12 and 24 hours (12 
hours for 6 A load application and 24 
hours for 10 A load applications). 
Factory delayed start setting: 24 hours 
 
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
24 hours
Delay
12 hours
Delay
30 seconds
(test)
Delay
 
Test Mode: 
Two switches are provided. One to reset the timer without 
interrupting the AC and one to reduce the starting delay to 
less than one minute.