Emerson MPR15 Series User Manual
106 Appendix B: NT5C10CO shelf
UM5C06B / C ( 169-2071-500 ) P0711722 Standard 10.00 May 2001
Technical specifications
WARNING
The power shelf must be connected to 120 V AC and a
20-ampere circuit. The AC receptacle must be rated 20
amperes and wired with #12 AWG. Non-conformance to
these requirement may cause the AC breaker/fuse at the
AC distribution cabinet to open, under certain operational
conditions, resulting in loss of power for both rectifiers.
Input AC:
120 V AC/18 A
Power system maximum load:
6 A typical to 10 A maximum.
Battery charging current:
7 to 11 A, depending on power system
load.
Maximum battery reserve:
120 AH (based on 8 hours).
Delayed Start delay:
Two positions; 12 and 24 hours (12
hours for 6 A load application and 24
hours for 10 A load applications).
Factory delayed start setting: 24 hours
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
6
5
4
3
2
1
OPEN
CLOSED
24 hours
Delay
Delay
12 hours
Delay
Delay
30 seconds
(test)
Delay
(test)
Delay
Test Mode:
Two switches are provided. One to reset the timer without
interrupting the AC and one to reduce the starting delay to
less than one minute.
interrupting the AC and one to reduce the starting delay to
less than one minute.